Order #: 2141.01
Mfg #: 2141.01
AEMC Instruments 6416 Ground Resistance Tester & Clamp Meter
Order #: 2141.01
Mfg #: 2141.01
Product Highlights
The Ground Resistance Tester Model 6416 measures ground rod and grid resistance and impedance without the use of auxiliary rods. Clamp-on ground resistance testers can be used in multi-grounded systems without disconnecting or de-energizing the ground system under test. The Model 6416 simply clamps around the grounding electrode or conductor and measures the resistance to ground. By performing measurements on intact ground systems, the user also verifies the quality of the grounding connections and bonds. Resistance and continuity of grounding loops around pads and buildings may also be measured.
- Contact Voltage Indication (Warns of Unsafe Conditions)
- Large Multi-Function Bright Yellow Organic Display (OLED)
- Selectable Test Frequency (Improves Accuracy in Inductive Environments)
- Storage of Measurements (O and/or A, V, Inductance with Time-Stamping)
- Model 6416: up to 300 Measurements Stored
- Designed to EN 61010-1, 600V CAT IV Safety Standards
- Clamping Diameter of 1.4” (35mm) with Large Jaw Design
- Displays Stored Measurements on the LCD Display
- Auto-Off Power Function
- Noise Icon And Buzzer Alert User to Presence of Dangerous Voltage and Current Levels
- Rugged Lexan® Head and Body Construction Resists Breakage
Note: *Replacement for AEMC 5717E
Each Unit Includes
- Hard Carrying Case
- Calibration Loop
- Four 1.5V AA Batteries
- User Manual
- AEMC Instruments 2141.50 Replacement Case, ABS w/Slot for 3710, 3731, 6416 & 6417Replacement Case,ABS w/Slot for 3710-3731,6416 & 6417
Order #: 2141.50
Mfg #: 2141.50
Availability: Ships in 1-2 weeksSpecial Price $131.67 Regular Price $138.60
Ground Resistance Measurement (Auto-Ranging 1 to 199Ω) | ||
Measurement Range | Resolution | Accuracy |
(0.010 to 0.099) Ω | 0.001 Ω | ±(1.5%Reading +0.01 Ω) |
(0.10 to 0.99) Ω | 0.01 Ω | ±(1.5%Reading +0.02 Ω) |
(1 to 49.9) Ω | 0.1 Ω | ±(1.5% Reading +0.1 Ω) |
(50.0 to 99.5) Ω | 0.5 Ω | ±(2% Reading +0.5 Ω) |
(100 to 199) Ω | 1 Ω | ±(3% Reading +1 Ω) |
( 200 to 395) Ω | 5 Ω | ±(5% Reading +5 Ω) |
(400 to 590) Ω | 10 Ω | ±(10% Reading +10 Ω) |
(600 to 1150) Ω | 50 Ω | 20% approx |
(1200 to 1500) Ω | 50 Ω | 25% approx |
Alarm | Adjustable from (1 to 199) Ω | |
Frequency Selection | Choice of (50, 60, 128, or 2083) Hz for impedance calculation | |
Maximum Overload | Permanent current: 100 max. 50/60 Hz Transient current: (<5 s) 200A 50/60 Hz |
|
Current Measurement Range (Auto-Ranging) | ||
Measurement Range | Resolution | Accuracy |
(0.200 to 0.999) mA | 1 µA | ±(2 % Reading +50 µA) |
(1.000 to 2.990) mA | 10 µA | ±(2 % Reading +50 µA) |
(3.00 to 9.99) mA | 10 µA | ±(2 % Reading +50 µA) |
(10.00 to 29.99) mA | 100 µA | ±(2 % Reading +100 µA) |
(30.0 to 99.9) mA | 100 µA | ±(2 % Reading +100 µA) |
(100 to 299.9) mA | 1 mA | ±(2 % Reading +1 mA) |
(0.300 to 0.990) A | 1 mA | ±(2 % Reading +1 mA) |
(1.000 to 2.999) A | 10 mA | ±(2 % Reading +10 mA) |
(3.00 to 39.99) A | 10 mA | ±(2 % Reading +10 mA) |
Loop Inductance Measurement | ||
Measurement range | Resolution | Accuracy |
(10 to 100) µH | 1 µH | ±(5 % Reading +1 µH) |
(100 to 500) µH | 1 µH | ±(3 % Reading +1 µH) |
Contact Voltage (Touch Voltage) Calculated | ||
Measurement range | Resolution | Accuracy |
(0.1 to 4.9) V | 0.1 V | ±(5 % Reading +0.1 V) |
(5.0 to 49.5) V | 0.5 V | ±(5 % Reading +0.5 V) |
(50 to 75.0) V | 1 V | ±(10 % Reading +1 V) |
General Features | ||
Display | OLED, 152 segments (48x39) mm | |
Memory | 300 measurements | |
Alarm | 3 separate alarms (Ω, V and A) | |
Power Source | (4) x1.5 V LR6 (AA) alkaline batteries or 4 NiMH batteries | |
Battery Life | 12 hours or 1440 30-seconds tests approx | |
Jaw Opening | 1.38 in (35 mm) max | |
Dimensions | (2.16 x 3.74 x 10.31) in (55 x 95 x 262) mm | |
Weight (with Battery) | 2.06 lbs (935 g) | |
Operating Temperature | (-4 to +131) °F (-20 to +55) °C | |
Storage Temperature | (-22 to +158) °F (-30 to +70) °C | |
Relative Humidity | Up to 90 % @ 40 °C | |
Ingress Protection (IP) | IP 40 | |
EMC | EN 61326-1 | |
Safety Compliance | IEC 61010-1, EN 61010-2-30, EN 61010-2-32, Pollution Degree 2, 600 V CAT IV |